183.330 - Distribution panels and switchboards.

  (a) Each distribution panel and switchboard must be in as dry a location as practicable, adequately ventilated, and protected from falling debris and dripping or splashing water.

  (b) Each distribution panel or switchboard must be totally enclosed and of the dead front type.

  (c) Each switchboard must be fitted with a dripshield.

  (d) Distribution panels and switchboards that are accessible from the rear must be constructed to prevent a person from accidentally contacting energized parts.

  (e) Working space must be provided around all main distribution panels and switchboards of at least 610 millimeters (24 inches) in front of the switchboard, and at least 455 millimeters (18 inches) behind the switchboard. Rear access is prohibited when the working space behind the switchboard is less than 455 millimeters (18 inches).

  (f) Nonconducting mats or grating must be provided on the deck in front of each switchboard and, if accessible from the rear, on the deck in the rear of the switchboard.

  (g) All uninsulated current carrying parts must be mounted on noncombustible, nonabsorbent, high dielectric insulating material.

  (h) Equipment mounted on a hinged door of an enclosure must be constructed or shielded so that a person will not accidentally contact energized parts of the door mounted equipment when the door is open and the circuit energized.

  (i) In the design of a control, interlock, or indicator circuit, the disconnect device and its connections, including each terminal block for terminating the vessel's wiring, must not have any electrically unshielded or uninsulated surfaces.

  (j) Switchboards and distribution panels must be sized in accordance with 111.3019(a) in subchapter J of this chapter.

[CGD 85080, 61 FR 997, Jan. 10, 1996, as amended by CGD 97057, 62 FR 51050, Sept. 30, 1997]

Other documents:
Johnetta Nelson Appellant v Upsala College Robert E Karsten George W Freyberger Warren H Funk. 51 F.... | United States of America Plaintiff-Appellee v Jose Corpuz Jr. Defendant-Appellant. 953 F.2d 526 9th Cir 1992 | lawrence v. van aken (6th cir. 2006) | Applications, hearings, determinations, etc.: Energy East Corp., | case of tribunal superior de justicia cáceres extremadura sala de lo social of july 31 2001 | Verordnung EG Nr 741/2004 der Kommission vom 21 April 2004 zur Festlegung der den Einführ... | Unpublished Disposition Notice Sixth Circuit Rule 24 C States that Citation of Unpublished Dispositi... | Auto of Tribunal Superior de Justicia - Bilbao, Pais Vasco - Sala de lo Contencioso-Administrativo, of June 20, 2005 | Case of Tribunal Superior de Justicia Madrid Sala de lo Contencioso-Administrativo of October 17 2003 | makor issues & rights ltd. et al. plaintiffs-appellants v tellabs inc. et al. defendants-appellees. 437 f.3d 588 7th cir 2006 | Atribulada diva del country | AUTOMOVILISMO Triunfo en Montmeló para Marc Gené